Frequency changed alarm was incorrectly disabled Transformer Ratio alarm was not working Invalid tap numbers are now ignored (instead of clamped), it uses last valid value Average Error for Ext Loop Max Error % is now squared and sqrt’d to avoid sign problems Dynamic NCC algorithm changed to account for Top and AutoLower logic New External Loop Disabled alarm (reports when ExtLoop is disabled for 60s) Balance uses same permissives as External Loop Substation tap changer end of life message was incorrectly generated Charge 1 reports AvgMW equal to ChargeMW For Z and R only regulation modes, I-Z/R Max Error % is used (Willie) R regulator clamps SP to >R_sc Fixed AdvancedControl configuration, it did not save changes properly ShadowMode bit is logged